Schneider Micom P127 Directional And Non-Directional Overcurrent Relay

SKU: MICOM P127 Categories: ,

Description

Schneider Micom P127

Schneider Micom P127 relay is part of MiCOM P12x, a range of directional and non-directional overcurrent relays from single-phase or earth fault up to the multifunctional three-phase P127 numerical relay with voltage protection functions. Models available: MiCOM P120, MiCOM P121, MiCOM P122, MiCOM P123, MiCOM P125, MiCOM P126, MiCOM P127

MiCOM P127 is housed in a compact 4U case in 20TE or 30TE widths, Schneider Micom P127 Relay is fully withdrawable to facilitate easy and quick replacement. The dual-rated current input is powered by conventional 1A or 5A Current Transformers. A wide-range power supply allows a flexible auxiliary voltage to be applied from 24-250Vdc/48-240Vac. P122 also offers a compact case solution with reduced hardware and functionality where installation space is minimal.

Software features include 2 settings groups for quick switching between application configurations and customizable reflex automation, allowing logical AND, OR, or NOT gates.

MiCOM P127 devices also include a rear RS485 communication port with a variety of protocols; DNP3, IEC 60870-5-103, Modbus, and Courier.

Schneider Micom P127 numerical relay Main Characteristics:

range of product MiCOM P127
device short name P127
relay application Feeder
protection type Overcurrent ANSI code: 50/51
Recloser ANSI code: 79
Cold load pick-up
Earth fault ANSI code: 50G/51G
Lockout ANSI code: 86
Negative sequence overvoltage ANSI code: 47
Undervoltage ANSI code: 27
Overvoltage ANSI code: 59
Rate of change of frequency ANSI code: 81R
Neutral voltage displacement ANSI code: 59N
Thermal overload protection ANSI code: 49RMS
Under frequency ANSI code: 81L
Phase undercurrent ANSI code: 37
Breaker failure ANSI code: 50BF
Negative sequence overcurrent ANSI code: 46
Restricted earth fault ANSI code: 64REF
Directional earth fault ANSI code: 67N
Directional phase overcurrent ANSI code: 67
Over frequency ANSI code: 81O
Voltage-restrained overcurrent ANSI code: 50V/51V
number of inputs 4 current input CT…X/5 A and X/1 A
3 voltage
12 discrete
number of outputs 9 discrete
communication port protocol DNP3
IEC 60870-5-103
Modbus RTU

 

Technical Details:

[Us] rated supply voltage 24…250 V DC 19.2…300 V
48…250 V DC 38.4…300 V
48…240 V AC 38.4…264 V
control and monitoring type Circuit breaker/contactor control
network and machine diagnosis type Fault recording
Event recording
Disturbance recording15 s
switchgear diagnosis type CT/VT supervision
Trip circuit supervision ANSI code: TCS
display type Backlit LCD: 2 lines of 16 characters
discrete input voltage 24…250 V DC 19.2 V standard variant
48…250 V AC 19.2 V standard variant
48…250 V DC 105 V further option
48…250 V DC 77 V further option
48…250 V DC 154 V further option
48…240 V AC 105 V further option
48…240 V AC 77 V further option
48…240 V AC 154 V further option
communication port support RS232
RS485
Complementary

 

Micom P127 Relay Environment:

type of measurement Current
height 177 mm total:
156 mm embedded:
width 155 mm
depth 249.6 mm total:
223 mm embedded:
device mounting Flush

 

Our catalog of Schneider Micom Protection Relays provides leading and reliable protection and control for any network application. The latest Protection Relays also offer comprehensive security and dependability for your electrical grid, from overcurrent and arc protection to distance and differential protection of the transmission line. Our product range offers solid protection with advanced communications such as the IEC 61850 to give you peace of mind in protecting your grid. Contact us to get the Schneider Micom P127 relay price!